BF-3085-2
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- Double Layer
- Minimum Substrate Thickness
- 100 mm
- FRL / FRR
- -/120/90
- Trade
- Plumbing / Hydraulic / Active Fire
- Service
- Plastic Pipes, UPVC
- Fire Rating
- 120
Fire-stopping products
Application dimensions
- Min Diameter
- 0 mm
- Max Diameter
- 110 mm
- Service Diameter Range
- Up to 110 mm
- Aperture
- 156 x 110 mm
- Annular Gap
- Fill area around pipe mm
- Sealant Depth
- 10 mm
Specimen size & details
Up to 110 mm uPVC pipe with 6.6 mm wall thickness. The pipe was installed at a 30° angle to the separating element through a 156 mm x 110 mm aperture. Sealant installed around service 10 mm deep in annular gap finished flush both sides. The system includes a 160 mm BOSS MaxiCollar™ installed to both sides.