BF-3099-7

System details

Type
Service Penetration
Element
Wall
Substrate
AAC / Hebel 
Minimum Substrate Thickness
78 mm
FRL / FRR
-/120/90
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-3099-7 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
110 mm
Service Diameter Range
Up to 110 mm
Annular Gap
2.5 mm
Sealant Depth
10 mm

Specimen size & details

Up to 110 mm uPVC DWV pipe with 3.5 mm wall thickness. FM-300 sealant applied on the joint between the collar and panel both sides. The system includes a 150 mm BOSS MaxiCollar™ installed to both sides.