BF-3161-4

System details

Type
Service Penetration
Element
Wall
Substrate
Concrete
Minimum Substrate Thickness
78 mm
FRL / FRR
-/120/90
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-3161-4 system drawing

Application dimensions

Min Diameter
100 mm
Max Diameter
100 mm
Service Diameter Range
100 mm
Aperture
Up to 1200 x 500 mm
Annular Gap
15 mm
Sealant Depth
Full depth mm

Specimen size & details

100 mm uPVC pipe with 3.3 mm maximum wall thickness, penetrating 2 layers of BOSS Batt™ protecting an aperture up to 1200 mm x 500 mm, installed through a 100 mm BOSS OneWay collar centrally located through the separating element. Sealant installed full depth in 15.0 mm annular gap between the 130 mm aperture and the in-wall collar.

Resources