BF-3161-4
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- Concrete
- Minimum Substrate Thickness
- 78 mm
- FRL / FRR
- -/120/90
- Trade
- Plumbing / Hydraulic / Active Fire
- Service
- Plastic Pipes, UPVC
- Fire Rating
- 120
Fire-stopping products
Application dimensions
- Min Diameter
- 100 mm
- Max Diameter
- 100 mm
- Service Diameter Range
- 100 mm
- Aperture
- Up to 1200 x 500 mm
- Annular Gap
- 15 mm
- Sealant Depth
- Full depth mm
Specimen size & details
100 mm uPVC pipe with 3.3 mm maximum wall thickness, penetrating 2 layers of BOSS Batt™ protecting an aperture up to 1200 mm x 500 mm, installed through a 100 mm BOSS OneWay collar centrally located through the separating element. Sealant installed full depth in 15.0 mm annular gap between the 130 mm aperture and the in-wall collar.