BF-3165-4

System details

Type
Service Penetration
Element
Wall
Substrate
Concrete
Minimum Substrate Thickness
100 mm
FRL / FRR
-/60/60
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
60

Fire-stopping products

BF-3165-4 system drawing

Application dimensions

Min Diameter
220 x 90 mm
Max Diameter
220 x 90 mm
Service Diameter Range
220 x 90 mm
Aperture
Up to 600 x 600 mm
Sealant Depth
Surface mm

Specimen size & details

220 mm x 90 mm uPVC duct with 2.0 mm maximum wall thickness, penetrating 2 layers of BOSS Batt™ protecting an aperture up to 600 mm x 600 mm. 3 layers of BOSS UniWrap™ or BOSS PWP Pipe Wrap flush with the face of the separating element on both sides. Sealant applied to the ends of the BOSS UniWrap™ or BOSS PWP Pipe Wrap on both sides.