BF-3166-4

System details

Type
Service Penetration
Element
Wall
Substrate
Concrete
Minimum Substrate Thickness
100 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-3166-4 system drawing

Application dimensions

Min Diameter
200 mm
Max Diameter
200 mm
Service Diameter Range
200 mm
Aperture
Up to 600 x 600 mm
Annular Gap
35 mm
Sealant Fillet
25 (Wall) x 40 (Pipe) mm

Specimen size & details

200 mm uPVC pipe with 7.7 mm maximum wall thickness, penetrating 2 layers of BOSS Batt™ protecting an aperture up to 600 mm x 600 mm. 5 layers of BOSS UniWrap™ or BOSS PWP Pipe Wrap flush with the face of the separating element on both sides. Fillet of sealant applied 25 mm wide (wall) x 40 mm deep (pipe) on both sides.