BF-3168-4

System details

Type
Service Penetration
Element
Wall
Substrate
Concrete
Minimum Substrate Thickness
116 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-3168-4 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
50 mm
Service Diameter Range
Up to 50 mm
Aperture
Up to 600 x 600 mm
Annular Gap
10 mm
Sealant Depth
26 mm

Specimen size & details

Up to 50 mm uPVC pipe with 3.5 mm maximum wall thickness, penetrating 2 layers of BOSS Batt™ protecting an aperture up to 600 mm x 600 mm. 2 layers of BOSS UniWrap™ or BOSS PWP Pipe Wrap encased in a metal sleeve, flush with the face of the separating element on both sides. Sealant 26 mm deep in 10.0 mm annular gap between the wall, service and metal sleeve, finished flush both sides.

Resources