BF-3172-8

System details

Type
Service Penetration
Element
Wall
Substrate
Pronto Panel 
Minimum Substrate Thickness
116 mm
FRL / FRR
-/120/90
Trade
Plumbing / Hydraulic / Active Fire
Service
CPVC
Fire Rating
120

Fire-stopping products

BF-3172-8 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
60.3 mm
Service Diameter Range
Up to 60.3 mm
Aperture
Up to 600 x 600 mm
Annular Gap
4.85 mm
Sealant Fillet
5 mm

Specimen size & details

Up to 60.3 mm cPVC pipe with 4.7 mm maximum wall thickness, penetrating 2 layers of BOSS Batt™ protecting an aperture up to 600 mm x 600 mm. 2 layers of BOSS UniWrap™ or BOSS PWP Pipe Wrap encased in a metal sleeve, flush with the face of the separating element on both sides. 5 mm x 5 mm fillet of sealant applied both sides.