BF-3180-25
System details
- Type
- Service Penetration
- Element
- Floor
- Substrate
- Concrete Slab
- Minimum Substrate Thickness
- 150 mm
- FRL / FRR
- -/60/60
- Trade
- Plumbing / Hydraulic / Active Fire
- Service
- Plastic Pipes, UPVC
- Fire Rating
- 60
Fire-stopping products
Application dimensions
- Min Diameter
- 200 mm
- Max Diameter
- 200 mm
- Service Diameter Range
- 200 mm
- Aperture
- Up to 600 x 600 mm
- Annular Gap
- 12 mm
- Sealant Depth
- 10 mm
Specimen size & details
Up to 200 mm uPVC pipe with 7.7 mm - 9.6 mm wall thickness, penetrating 1 layer of BOSS Batt™ protecting an aperture up to 600 mm x 600 mm. 10 layers of BOSS UniWrap™ or BOSS PWP Pipe Wrap mid-depth of the floor. Sealant 10.0 mm deep in 12.0 mm annular gap to the top side.