BF-3210-33

System details

Type
Blank Seal
Element
Floor
Substrate
Cross Laminated Timber (CLT)
Minimum Substrate Thickness
110 mm
FRL / FRR
-/60/60
Trade
Construction (Linear Gaps / Blank Seals)
Service
Other
Fire Rating
60

Fire-stopping products

BF-3210-33 system drawing

Application dimensions

Max Width
250 mm
Max Length
250 mm
Aperture
250 x 250 mm
Sealant Fillet
10 mm

Specimen size & details

Aperture size of 250 mm x 250 mm in the CLT slab. A 252 mm x 252 mm BOSS Batt™ friction fitted into the opening. The BOSS batt is to be recessed 20 mm from the bottom edge of the slab, with a 10 mm x 10 mm fillet of BOSS FireMastic-300™ around the edges on the underside.