BF-3248-2

System details

Type
Service Penetration
Element
Wall
Substrate
Double Layer
Minimum Substrate Thickness
118 mm
FRL / FRR
-/60/60
Trade
Plumbing / Hydraulic / Active Fire
Service
Water Valves & Tap Sets
Fire Rating
60

Fire-stopping products

BF-3248-2 system drawing

Application dimensions

Min Diameter
20 mm
Max Diameter
20 mm
Service Diameter Range
20 mm
Aperture
45.3 mm
Annular Gap
8.7 - 15.6 mm
Sealant Depth
13 mm

Specimen size & details

1 - sided penetration. 20 mm x 1/2" External Wingback Elbow (Brass) penetrating the wall from either direction. Wingback fixed to a 300 mm wide x 200 mm high x 20 mm thick plywood backing. BOSS FireMastic-EMA™ sealant 13 mm deep in the annular gap finished flush.