BF-3291-27

System details

Type
Service Penetration
Element
Ceiling
Substrate
Fire Rated Plasterboard
Minimum Substrate Thickness
235 mm
FRL / FRR
-/90/90 - RISF 54 min
Trade
Electrical
Service
Multicore / Mains / Orange Circular
Fire Rating
90

Fire-stopping products

BF-3291-27 system drawing

Application dimensions

Aperture
51 mm
Sealant Depth
Top 19 Bottom 26 mm

Specimen size & details

10.6 mm diameter Main power cable. BOSS FireMastic-HPE™ sealant 26 mm deep in annular gap of plasterboard finished flush on the underside. BOSS FireMastic-300™ sealant 19 mm deep in annular gap of particle board flooring on the top side, finished flush.

Resources