BF-3298-5

System details

Type
Service Penetration
Element
Wall
Substrate
Masonry
Minimum Substrate Thickness
144 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Sprinkler Pipe
Fire Rating
120

Fire-stopping products

BF-3298-5 system drawing

Application dimensions

Min Diameter
34 mm
Max Diameter
34 mm
Service Diameter Range
34 mm
Aperture
42 mm
Annular Gap
4 mm
Sealant Depth
26 mm
Sealant Fillet
50 mm

Specimen size & details

34 mm diameter (25NB) galvanised steel sprinkler pipe with 3.5 mm wall thickness. BOSS FireMastic-300™ sealant 26 mm deep in the annular gap with 50 mm x 50 mm fillet of sealant applied both sides.