BF-3311-4

System details

Type
Service Penetration
Element
Wall
Substrate
Concrete
Minimum Substrate Thickness
96 mm
FRL / FRR
-/90/90
Trade
Electrical
Service
Appendix D1 Config
Fire Rating
90

Fire-stopping products

BF-3311-4 system drawing

Application dimensions

Aperture
300 wide x 40 high mm
Sealant Fillet
50 mm

Specimen size & details

Partial Appendix D1 Group A cable configuration, consisting of:
- 3 x 3C+E 6 mm² cables
- 8 x 3C+E 16 mm² cables
Cable installed onto a 300 mm wide cable tray. The system installed within a 300 mm wide x 40 mm high aperture sealed with 50 mm x 50 mm fillet of BOSS FireMastic-300™ on both sides. 2 layers of BOSS P40-MAK Wrap™ wrapped around the system 300 mm on both sides from the sealant edge.

Resources