BF-3340-23
System details
- Type
- Linear Joint
- Element
- Wall
- Substrate
- BOSS Batt Sgl
- Minimum Substrate Thickness
- 50 mm
- FRL / FRR
- -/120/90
- Trade
- Construction (Linear Gaps / Blank Seals)
- Fire Rating
- 120
Fire-stopping products
Specimen size & details
Control joint. 1 strip of 100 mm wide BOSS Batt™ installed over a joint in the main BOSS Batt™ substrate, each side of the wall. Cut edges to be coated with layer of BOSS Ablative Coating™. The batt strips were fixed to the separating element with 90 mm pigtail screws, approximately 25 mm from the top and bottom edge of the batt strip, at 300 mm centres.