BF-3403-25

System details

Type
Linear Joint
Element
Floor
Substrate
Concrete Slab
Minimum Substrate Thickness
250 mm
FRL / FRR
-/120/120
Trade
Construction (Linear Gaps / Blank Seals)
Service
Other
Fire Rating
120

Fire-stopping products

BF-3403-25 system drawing

Application dimensions

Max Width
150 mm
Max Length
150 mm
Aperture
150 mm

Specimen size & details

170 mm wide × 100 mm deep BOSS FireStrip-ALX™ linear gap seal friction fitted within a 150 mm wide linear gap, positioned at mid-depth of the floor system.