BF-3415-25
System details
- Type
- Linear Joint
- Element
- Floor
- Substrate
- Concrete Slab
- Minimum Substrate Thickness
- 250 mm
- FRL / FRR
- -/120/60
- Trade
- Construction (Linear Gaps / Blank Seals)
- Service
- Other
- Fire Rating
- 120
Fire-stopping products
Application dimensions
- Max Width
- 100 mm
- Max Length
- 100 mm
- Aperture
- 100 mm
Specimen size & details
126 mm wide × 100 mm deep BOSS FireStrip-ALX™ linear gap seal friction fitted within a 100 mm wide linear gap, positioned 25 mm from the unexposed side of the floor system.