BF-3485-26

System details

Type
Service Penetration
Element
Floor
Substrate
AAC Floor
Minimum Substrate Thickness
150 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

System preview unavailable

Application dimensions

Min Diameter
200 mm
Max Diameter
200 mm
Service Diameter Range
200 mm
Aperture
1400 x 700 mm

Specimen size & details

200 mm uPVC pipe with 9.6 mm maximum wall thickness, penetrating a maximum 1400 mm x 700 mm aperture filled with 100 mm thick BOSS FireMortar-360™ gypsum based mortar, flush with the top face of the floor. 10-layers of BOSS UniWrap™ cast into the BOSS FireMortar-360™ at mid-depth. 10 mm wide x 10 mm deep gap around the service filled with BOSS FireMastic-300™ on the underside.

Resources