BF-3488-26

System details

Type
Service Penetration
Element
Floor
Substrate
AAC Floor
Minimum Substrate Thickness
150 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
PE
Fire Rating
120

Fire-stopping products

System preview unavailable

Application dimensions

Min Diameter
125 mm
Max Diameter
125 mm
Service Diameter Range
125 mm
Aperture
1400 x 700 mm

Specimen size & details

125 mm PE pipe with 3.1 mm maximum wall thickness, penetrating a maximum 1400 mm x 700 mm aperture filled with 100 mm thick BOSS FireMortar-360™ gypsum based mortar, flush with the top face of the floor. 125 mm BOSS MaxiCollar™ installed on the underside. 10 mm wide x 5 mm deep gap around the service filled with BOSS FireMastic-300™ on the underside.

Resources