BF-3494-25

System details

Type
Service Penetration
Element
Floor
Substrate
Concrete Slab
Minimum Substrate Thickness
150 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

System preview unavailable

Application dimensions

Min Diameter
160 mm
Max Diameter
160 mm
Service Diameter Range
160 mm
Aperture
1400 x 700 mm

Specimen size & details

160 mm uPVC pipe with 6.2 - 9.5 mm maximum wall thickness, penetrating a maximum 1400 mm x 700 mm aperture filled with 100 mm thick BOSS FireMortar-360™ gypsum based mortar, flush with the top face of the floor. 160 mm BOSS MaxiCollar™ installed on the underside. 10 mm wide x 5 mm deep gap around the service filled with BOSS FireMastic-300™ on both sides.

Resources