BF-3504-2

System details

Type
Service Penetration
Element
Wall
Substrate
Double Layer
Minimum Substrate Thickness
100 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

System preview unavailable

Application dimensions

Min Diameter
125 mm
Max Diameter
125 mm
Service Diameter Range
125 mm
Aperture
295 x 215 mm

Specimen size & details

125 mm PVC pipe with 7.4 mm aperture filled with 100 mm thick BOSS FireMortar-360™ gypsum based mortar. 4-layers of BOSS UniWrap™ installed around the service flush to each face of the wall system.