BF-3505-2

System details

Type
Service Penetration
Element
Wall
Substrate
Double Layer
Minimum Substrate Thickness
100 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
PP
Fire Rating
120

Fire-stopping products

System preview unavailable

Application dimensions

Min Diameter
50 mm
Max Diameter
50 mm
Service Diameter Range
50 mm
Aperture
295 x 215 mm

Specimen size & details

50 mm PP pipe with 3.1 mm maximum wall thickness, penetrating a maximum 295 mm x 215 mm aperture filled with 100 mm thick BOSS FireMortar-360™ gypsum based mortar. 4-layers of BOSS UniWrap™ installed around the service flush to each face of the wall system.