BF-2035-13

System details

Type
Service Penetration
Element
Wall
Substrate
BOSS Batt Dbl – Friction 
Minimum Substrate Thickness
75 mm
FRL / FRR
-/120/120
Trade
Electrical
Service
TPS
Fire Rating
120

Fire-stopping products

BF-2035-13 system drawing

Application dimensions

Aperture
90 mm
Sealant Depth
Full depth mm
Sealant Fillet
0 mm

Specimen size & details

Up to 22 x 2.5 mm², 2C+E TPS Power Cables. Sealant full depth of the wall in annular gap finished flush on both sides. Wall system to include an additional build-up of 13 mm thick FR plasterboard locally around the service.