BF-2043-25
System details
- Type
- Service Penetration
- Element
- Floor
- Substrate
- Concrete Slab
- Minimum Substrate Thickness
- 150 mm
- FRL / FRR
- -/180/120
- Trade
- Electrical
- Service
- Multicore / Mains / Orange Circular
- Fire Rating
- 180
Fire-stopping products
Application dimensions
- Aperture
- 200 x 200 mm
- Sealant Depth
- 25 mm
- Sealant Fillet
- 0 mm
Specimen size & details
•10 × (A1) small sheathed (PVC/PVC) 5 x 1.5 mm2,
•10 × (A2) small sheathed (EPR/PO) 5 × 1.5 mm2,
•10 × (A3) small sheathed (XLPE/EVA) 5 × 1.5 mm2.
Sealant 25 mm deep finished flush with upper face of floor. The system also includes a 100 mm deep infill friction fitted stone wool insulation, centrally located in the annular gap through the floor system.
P40 MAK Wrap to be installed 600 mm on both sides.