BF-2045-26

System details

Type
Service Penetration
Element
Floor
Substrate
AAC Floor
Minimum Substrate Thickness
150 mm
FRL / FRR
-/240/30
Trade
Electrical
Service
Telecomm
Fire Rating
240

Fire-stopping products

BF-2045-26 system drawing

Application dimensions

Aperture
200 x 200 mm
Sealant Depth
25 mm
Sealant Fillet
0 mm

Specimen size & details

•100 mm diameter (F) cable bundle (telecommunication cable) (PE/PE) 20 mm x 2 mm x 0.6 mm2 screened.
Sealant 25mm deep in annular gap finished flush on both sides. The system also includes a 100 mm deep infill friction fitted stone wool insulation, centrally located in the annular gap through the floor system.