BF-2073-4

System details

Type
Service Penetration
Element
Wall
Substrate
Concrete
Minimum Substrate Thickness
100 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Insulated Copper Pipe
Fire Rating
120

Fire-stopping products

BF-2073-4 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
159 mm
Service Diameter Range
Up to 159 mm
Aperture
263 mm
Sealant Depth
25 mm
Sealant Fillet
10 mm

Specimen size & details

Up to 159 mm copper pipe with 32 mm thick Armaflex insulation. Insulation wrapping is extended 1000 mm on both sides. Sealant 25 mm deep in annular gap and finished with a 10 mm x 10 mm fillet on both sides.

Resources