BF-2082-7
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- AAC / Hebel
- Minimum Substrate Thickness
- 100 mm
- FRL / FRR
- -/60/60
- Trade
- Plumbing / Hydraulic / Active Fire
- Service
- Insulated Steel Pipe
- Fire Rating
- 60
Fire-stopping products
Application dimensions
- Min Diameter
- 0 mm
- Max Diameter
- 150 mm
- Service Diameter Range
- Up to 150 mm
- Aperture
- Up to 600 x 600 mm
- Annular Gap
- 7.5 mm
- Sealant Depth
- 15 mm
- Sealant Fillet
- 0 mm
Specimen size & details
Up to 150 mm steel or iron pipe with 30 mm thick foil faced glass wool insulation, installed through 100 mm thick double layer of BossBatt in maximum aperture 600 mm x 600 mm. Insulation wrapping is extended 1000 mm on both sides. Sealant 15 mm deep in annular gap and finished flush on both sides.