BF-2101-25

System details

Type
Service Penetration
Element
Floor
Substrate
Concrete Slab
Minimum Substrate Thickness
150 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2101-25 system drawing

Application dimensions

Min Diameter
50 mm
Max Diameter
50 x 3.7 mm
Service Diameter Range
50 mm
Annular Gap
20 mm
Sealant Depth
25 mm
Sealant Fillet
0 mm

Specimen size & details

50 mm x 3.7 mm wall thickness PVC pipe. Sealant 25 mm deep in annular gap finished flush both sides. The sealant was supported by 10 mm diam. Polyethylene back rods.