BF-2109-13

System details

Type
Service Penetration
Element
Wall
Substrate
BOSS Batt Dbl – Friction 
Minimum Substrate Thickness
116 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2109-13 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
25 mm
Service Diameter Range
Up to 25 mm
Annular Gap
0 mm
Sealant Depth
0 mm
Sealant Fillet
20 mm

Specimen size & details

Up to 25 mm uPVC pipe. No annular gap. Sealant installedin annular gap with 20 mm x 20 mm fillet on both sides.