BF-2110-4

System details

Type
Service Penetration
Element
Wall
Substrate
Concrete
Minimum Substrate Thickness
116 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2110-4 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
32 mm
Service Diameter Range
Up to 32 mm
Annular Gap
20 mm
Sealant Depth
25 mm
Sealant Fillet
20 mm

Specimen size & details

Up to 32 mm uPVC pipe. Sealant depth of plasterboard in annular gap with and a 20 mm x 20 mm fillet on both sides.