BF-2113-5

System details

Type
Service Penetration
Element
Wall
Substrate
Masonry
Minimum Substrate Thickness
144 mm
FRL / FRR
-/90/90
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
90

Fire-stopping products

BF-2113-5 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
80 mm
Service Diameter Range
Up to 80 mm
Annular Gap
20 mm
Sealant Depth
25 mm
Sealant Fillet
0 mm

Specimen size & details

Up to 80 mm uPVC pipe. Sealant depth of plasterboard in annular gap finished flush on both sides.