BF-2116-13
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- BOSS Batt Dbl – Friction
- Minimum Substrate Thickness
- 100 mm
- FRL / FRR
- -/60/60
- Trade
- Plumbing / Hydraulic / Active Fire
- Service
- Plastic Pipes, UPVC
- Fire Rating
- 60
Fire-stopping products
Application dimensions
- Min Diameter
- 0 mm
- Max Diameter
- 125 mm
- Service Diameter Range
- Up to 125 mm
- Annular Gap
- 20 mm
- Sealant Depth
- 25 mm
- Sealant Fillet
- 10 mm
Specimen size & details
Up to 125 x 9.2 mm wall thickness uPVC pipe. Sealant to depth of plasterboard in 20 mm annular gap with additional 10 mm × 10 mm fillet both sides.