BF-2118-16

System details

Type
Service Penetration
Element
Wall
Substrate
Speedpanel / Korok (w/Buildup)
Minimum Substrate Thickness
128 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2118-16 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
43 mm
Service Diameter Range
Up to 43 mm
Annular Gap
23.5 mm
Sealant Depth
25 mm
Sealant Fillet
0 mm

Specimen size & details

Up to 43 mm uPVC pipe. Sealant to depth of plasterboard in 23.5 mm annular gap finished flush both sides.