Type
Service Penetration
Element
Wall
Substrate
BOSS Batt Dbl – Friction 
Minimum Substrate Thickness
120 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2121-13 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
40 mm
Service Diameter Range
Up to 40 mm
Annular Gap
10 mm
Sealant Depth
25 mm
Sealant Fillet
0 mm

Specimen size & details

Tested Uncapped/Capped - Up to 40 x 3.0 mm wall thickness uPVC pipe. Sealant to depth of plasterboard in 16 mm annular gap finished flush both sides.