BF-2130-13

System details

Type
Service Penetration
Element
Wall
Substrate
BOSS Batt Dbl – Friction 
Minimum Substrate Thickness
144 mm
FRL / FRR
-/120/30
Trade
Plumbing / Hydraulic / Active Fire
Service
PEX AL
Fire Rating
120

Fire-stopping products

BF-2130-13 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
25 mm
Service Diameter Range
Up to 25 mm
Annular Gap
20 mm
Sealant Depth
25 mm
Sealant Fillet
0 mm

Specimen size & details

Up to 25 mm PEX/AL/PEX pipe. Sealant to depth of plasterboard in up to 20 mm annular gap finished flush both sides.

Resources