BF-2136-20

System details

Type
Service Penetration
Element
Wall
Substrate
Shaftliner (w/Buildup)
Minimum Substrate Thickness
116 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
PEX
Fire Rating
120

Fire-stopping products

BF-2136-20 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
25 mm
Service Diameter Range
Up to 25 mm
Annular Gap
10 mm
Sealant Depth
25 mm
Sealant Fillet
0 mm

Specimen size & details

Up to 25 mm PE-Xa pipe. Sealant to depth of plasterboard in 10 mm annular gap finished flush both sides.

Resources