BF-2141-12

System details

Type
Service Penetration
Element
Wall
Substrate
Shaftliner 
Minimum Substrate Thickness
128 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
PEX
Fire Rating
120

Fire-stopping products

BF-2141-12 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
20 mm
Service Diameter Range
Up to 20 mm
Annular Gap
17.5 mm
Sealant Depth
26 mm
Sealant Fillet
0 mm

Specimen size & details

1-sided installation. System is approved for installation in both directions through the double layer plasterboard.
Up to 20 mm PE-Xa pipe. Sealant to depth of plasterboard in 17.5 mm annular gap finished flush.

Resources