BF-2142-2

System details

Type
Service Penetration
Element
Wall
Substrate
Double Layer
Minimum Substrate Thickness
100 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2142-2 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
40 mm
Service Diameter Range
Up to 40 mm
Aperture
80 mm
Sealant Depth
25 mm
Sealant Fillet
10 mm

Specimen size & details

1-sided installation. System is approved for installation in both directions.
Up to 40 mm x 1.9 mm wall thickness PVC pipe. Sealant to depth of plasterboard in annular gap with 10 mm x 10 mm fillet.