BF-2151-13

System details

Type
Service Penetration
Element
Wall
Substrate
BOSS Batt Dbl – Friction 
Minimum Substrate Thickness
75 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
PEX
Fire Rating
120

Fire-stopping products

BF-2151-13 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
32 mm
Service Diameter Range
Up to 32 mm
Aperture
60 mm
Annular Gap
14 mm
Sealant Depth
25 mm
Sealant Fillet
20 mm

Specimen size & details

Up to 32 mm PE-Xa pipe. Sealant to depth of 25 mm in annular gap both sides, with 20 mm x 20 mm fillet both sides.