BF-2159-14
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- BOSS Batt Dbl – Pattress
- Minimum Substrate Thickness
- 75 mm
- FRL / FRR
- -/120/120
- Trade
- Plumbing / Hydraulic / Active Fire
- Service
- Plastic Pipes, UPVC
- Fire Rating
- 120
Fire-stopping products
Application dimensions
- Min Diameter
- 0 mm
- Max Diameter
- 20 mm
- Service Diameter Range
- Up to 20 mm
- Aperture
- 24 mm
- Annular Gap
- 2 mm
- Sealant Depth
- Surface only mm
- Sealant Fillet
- 0 mm
Specimen size & details
Up to 20 mm uPVC pipe. Surface seal only on both sides.