BF-2159-4

System details

Type
Service Penetration
Element
Wall
Substrate
Concrete
Minimum Substrate Thickness
75 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2159-4 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
20 mm
Service Diameter Range
Up to 20 mm
Aperture
24 mm
Annular Gap
2 mm
Sealant Depth
Surface only mm
Sealant Fillet
0 mm

Specimen size & details

Up to 20 mm uPVC pipe. Surface seal only on both sides.