BF-2160-7

System details

Type
Service Penetration
Element
Wall
Substrate
AAC / Hebel 
Minimum Substrate Thickness
75 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2160-7 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
25 mm
Service Diameter Range
Up to 25 mm
Aperture
40 mm
Annular Gap
7.5 mm
Sealant Depth
25 mm
Sealant Fillet
20 mm

Specimen size & details

Up to 25 mm uPVC pipe. Sealant to depth of 25 mm in annular gap both sides, with 20 mm x 20 mm fillet both sides.