BF-2161-13

System details

Type
Service Penetration
Element
Wall
Substrate
BOSS Batt Dbl – Friction 
Minimum Substrate Thickness
75 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2161-13 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
32 mm
Service Diameter Range
Up to 32 mm
Aperture
73 mm
Annular Gap
20.5 mm
Sealant Depth
20 mm
Sealant Fillet
15 mm

Specimen size & details

Up to 32 mm uPVC pipe. Sealant to depth of 20 mm in annular gap both sides, with 15 mm x 15 mm fillet both sides.