BF-2162-13
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- BOSS Batt Dbl – Friction
- Minimum Substrate Thickness
- 75 mm
- FRL / FRR
- -/120/120
- Trade
- Plumbing / Hydraulic / Active Fire
- Service
- Plastic Pipes, UPVC
- Fire Rating
- 120
Fire-stopping products
Application dimensions
- Min Diameter
- 30 mm
- Max Diameter
- 40 mm
- Service Diameter Range
- 30-40 mm
- Aperture
- 44 mm
- Annular Gap
- 7 - 2 mm
- Sealant Depth
- 10 mm
- Sealant Fillet
- 25 mm
Specimen size & details
30 mm - 40 mm uPVC pipe. Sealant to depth of 10 mm in annular gap both sides, with 25 mm x 25 mm fillet both sides. The wall is to be built up with minimum 13 mm thick fire rated plasterboard on one side.