BF-2162-13

System details

Type
Service Penetration
Element
Wall
Substrate
BOSS Batt Dbl – Friction 
Minimum Substrate Thickness
75 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2162-13 system drawing

Application dimensions

Min Diameter
30 mm
Max Diameter
40 mm
Service Diameter Range
30-40 mm
Aperture
44 mm
Annular Gap
7 - 2 mm
Sealant Depth
10 mm
Sealant Fillet
25 mm

Specimen size & details

30 mm - 40 mm uPVC pipe. Sealant to depth of 10 mm in annular gap both sides, with 25 mm x 25 mm fillet both sides. The wall is to be built up with minimum 13 mm thick fire rated plasterboard on one side.