BF-2170-7

System details

Type
Service Penetration
Element
Wall
Substrate
AAC / Hebel 
Minimum Substrate Thickness
100 mm
FRL / FRR
-/120/120
Trade
Plumbing / Hydraulic / Active Fire
Service
Plastic Pipes, UPVC
Fire Rating
120

Fire-stopping products

BF-2170-7 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
50 x 2.4 mm
Service Diameter Range
Up to 50 mm
Aperture
Up to 600 x 600 mm
Annular Gap
20 mm
Sealant Depth
25 mm
Sealant Fillet
0 mm

Specimen size & details

Approved for Uncapped/Capped - 50 mm x 2.4 mm wall thickness uPVC pipe installed through 100 mm thick double layer of BossBatt aperture in separating element, with factory applied BOSS Ablative coating to both faces and PS coating to exposed face. Sealant depth of 25mm in annular gap finished flush. Maximum aperture 600 mm x 600 mm.