BF-2174-27

System details

Type
Service Penetration
Element
Ceiling
Substrate
Fire Rated Plasterboard
Minimum Substrate Thickness
235 mm
FRL / FRR
-/90/90 - 45 RISF
Trade
Plumbing / Hydraulic / Active Fire
Service
UPVC (Plastic Pipes)
Fire Rating
90

Fire-stopping products

BF-2174-27 system drawing

Application dimensions

Min Diameter
0 mm
Max Diameter
25 mm
Service Diameter Range
Up to 25 mm
Annular Gap
19 mm
Sealant Depth
26 mm
Sealant Fillet
0 mm

Specimen size & details

Up to 25 mm PVC pipe. Sealant to full depth of plasterboard ceiling in annular gap finished flush on the underside. BOSS FM300 sealant was also used to seal the particle board flooring to its full depth in the annular gap on the top side, finished flush. The specimen also achieved RSIF of 55 minutes.

Resources