BF-2192-13

System details

Type
Service Penetration
Element
Wall
Substrate
BOSS Batt Dbl – Friction 
Minimum Substrate Thickness
90 mm
FRL / FRR
-/60/60
Trade
HVAC
Service
HVAC Bundles
Fire Rating
60

Fire-stopping products

BF-2192-13 system drawing

Application dimensions

Aperture
80 mm
Sealant Depth
26 mm

Specimen size & details

- Paircoil - Up to 10 mm/15 mm insulated copper pipes with non-rated lagging,
- Up to 2.5 mm² 2C+E TPS Power Cable,
- Up to 1.5 mm² 2 Core Data Cable.
- Up to 20 mm uPVC outlet pipe
13 mm plasterboard patch (patress) 150 mm x 150 mm placed over the penetration on both sides, fixed to the wall. The edges of the plasterboard build up coated with a 13 mm x 13 mm fillet of FM300. HPE sealant in the annular gap 26 mm deep finished flush with the wall.