BF-2192-13
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- BOSS Batt Dbl – Friction
- Minimum Substrate Thickness
- 90 mm
- FRL / FRR
- -/60/60
- Trade
- HVAC
- Service
- HVAC Bundles
- Fire Rating
- 60
Fire-stopping products
Application dimensions
- Aperture
- 80 mm
- Sealant Depth
- 26 mm
Specimen size & details
- Paircoil - Up to 10 mm/15 mm insulated copper pipes with non-rated lagging,
- Up to 2.5 mm² 2C+E TPS Power Cable,
- Up to 1.5 mm² 2 Core Data Cable.
- Up to 20 mm uPVC outlet pipe
13 mm plasterboard patch (patress) 150 mm x 150 mm placed over the penetration on both sides, fixed to the wall. The edges of the plasterboard build up coated with a 13 mm x 13 mm fillet of FM300. HPE sealant in the annular gap 26 mm deep finished flush with the wall.