BF-2193-5

System details

Type
Service Penetration
Element
Wall
Substrate
Masonry
Minimum Substrate Thickness
90 mm
FRL / FRR
-/60/60
Trade
HVAC
Service
HVAC Bundles
Fire Rating
60

Fire-stopping products

BF-2193-5 system drawing

Application dimensions

Aperture
80 mm
Sealant Depth
13 mm
Sealant Fillet
0 mm

Specimen size & details

- Paircoil - Up to 10 mm/15 mm Insulated Copper Pipes with non-rated lagging,
- Up to 2.5mm² 2C+E TPS Power Cable,
- Up to 1.5mm² 2 Core Data Cable.
Boss MaxiCollar fixed to both sides of the wall. Sealant in the annular gap 13 mm deep finished flush. Sealant also to be applied to the annular gap between the services and collar to the depth of the collar finished flush.

Resources