BF-2199-13
System details
- Type
- Service Penetration
- Element
- Wall
- Substrate
- BOSS Batt Dbl – Friction
- Minimum Substrate Thickness
- 116 mm
- FRL / FRR
- -/60/60
- Trade
- HVAC
- Service
- HVAC Bundles
- Fire Rating
- 60
Fire-stopping products
Application dimensions
- Aperture
- 80 mm
- Sealant Depth
- 13 mm
- Sealant Fillet
- 0 mm
Specimen size & details
- Paircoil - Up to 10 mm/15 mm Insulated Copper Pipes with non-rated lagging,
- Up to 2.5 mm² 2C+E TPS Power Cable,
- Up to 1.5 mm² 2 Core Data Cable.
Boss MaxiCollar fixed to both sides of the wall. Sealant in the annular gap 13 mm deep finished flush. Sealant also to be applied to the annular gap between the services and collar to the depth of the collar finished flush both sides.