BF-2202-13

System details

Type
Service Penetration
Element
Wall
Substrate
BOSS Batt Dbl – Friction 
Minimum Substrate Thickness
116 mm
FRL / FRR
-/120/120
Trade
HVAC
Service
HVAC Bundles
Fire Rating
120

Fire-stopping products

BF-2202-13 system drawing

Application dimensions

Aperture
Up to 125 mm
Sealant Depth
25 mm
Sealant Fillet
25 mm

Specimen size & details

- Up to 3 x 20 mm Copper Pipes insulated with Armaflex foamed nitrile rubber wrap
- TPS cable
- Data cable
- Up to 20 mm PVC conduit.
Sealant to a depth of 25 mm in annular gap with 25 mm x 25 mm fillet on both sides. Sealant backed with foam backing rod. .

Resources