BF-2213-25

System details

Type
Service Penetration
Element
Floor
Substrate
Concrete Slab
Minimum Substrate Thickness
150 mm
FRL / FRR
-/240/120
Trade
HVAC
Service
HVAC Bundles
Fire Rating
240

Fire-stopping products

BF-2213-25 system drawing

Application dimensions

Aperture
150 mm
Sealant Depth
25 mm
Sealant Fillet
0 mm

Specimen size & details

- Up to 1 1/8" (28.3 mm) copper pipe with 25 mm thick E-Flex ST lagging
- Up to 7/8" (22 mm) copper pipe with 25 mm thick E-Flex ST lagging
- Up to 1 x 18 mm copper pipe with 19 mm thick lagging
- Up to 1 x 20 mm uPVC condensate pipe (WT 1.5 mm).
- Up to 2 x 2.5 mm² 3C+E TPS Power Cable
- Up to 2 x 2.5 mm² 2C+E TPS Power Cable
- Istrolex control cable
Sealant to depth of 25 mm in annular gap to backing rod finished flush both sides.